| OCS 100 Occupancy Sensors |
|
| OCS 100C |
| Square feet coverage area | 2000 square feet |
| |  |
| NOTE | These coverage dimensions are achieved when the OCS 100C is installed 10 ft (3.04 m) above the coverage area. |
|
|
| OCS 100W |
| Square feet coverage area | 1600 square feet |
| |  |
|
| Sensor |
| InteliDAPT® technology | Auto reset from test setting
Self-adjusting timer
Self-adjusting passive infrared thresholds
Automatic false-on and false-off correction |
| LED lamp | Red - infrared motion
Green - ultrasonic detection |
| Timer timeout | |
| OCS 100C | Automatic mode: 8 to 42 minutes (self-adjusts based on occupancy)
Manual mode: 8 to 42 minutes
Test mode: 8 seconds |
| OCS 100W | Automatic mode: 4 to 30 minutes (self-adjusts based on occupancy)
Manual mode: 4, 8, 15 and 30 minutes
Test mode: 8 seconds |
| Ultrasonic (US) | |
| OCS 100C | 4 sensors - 32 kHz output |
| OCS 100W | 2 sensors - 32 kHz output |
| Passive infrared (PIR) | |
| OCS 100C | Dual-element pyrometer and 12-element cylindrical segmented Fresnel lens, integral filter excludes excess PIR energy from sunlight |
| OCS 100W | Dual-element pyrometer and 12-element cylindrical rugged lens |
|
| Relay |
| Relay | 1 Normally Open and Closed contact, single pole, double throw 500 mA rated at 24 VDC, three-wire isolated relay |
|
| Photocell |
| Photocell | Adjustable natural-light override ranges from 1 to 100 foot-candles (10 to 1000 Lux) |
|
| Adaptive functions |
| Learning | 4 weeks for response error conditions, air current adaption and timer optimization |
| Post-learning occupancy periods | 24-hour circadian occupancy periods learned |
| Adjustments in post-learning period | Generally occupied periods
Generally unoccupied periods |
|
| Digital output |
| Quantity/type | 2 digital outputs |
| Connectors | Blue wire = Occupancy only
Gray wire = Occupancy + Photocell |
| Output voltage range | 0 - 24 VDC
Active high logic control signal with short-circuit protection, open collector when unoccupied |
|
| General |
| Sensor power input requirements | 20-24 VDC, 33 mA nominal
Power supply is not included. |
| NOTE | If power supplied is 12 VDC or USB-C 5V, use the included PC 1224 to convert 12 VDC or USB-C 5V to 24 VDC. |
|
| PC 1224 power requirements | Power Converter (included)
Input: USB-C 5V input
12 VDC, 1.5 A max
Output: 12 VDC, 1.25 A max
24 VDC, 75 mA max |
| NOTE | The PC 1224 power converter is included with the OCS 100. External Power supply is not included. |
|
| Power consumption — OCS 100C and OCS 100W | |
| Device | 0.8 W |
| Device and PC 1224 | 1.1 W |
| Device, PC 1224, and power supply | 1.4 W |
| Wiring | Color coded, pre-stripped leads - 6" (15 am) in total length |
| Ambient temperature/humidity | Operation: +32 to +104 °F (0 to +40 °C) / 0% to 95 %, noncondensing
For indoor use only |
| Cooling | Convection, no vents |
| Thermal dissipation — OCS 100C and OCS 100W | |
| Device | 2.6 BTU/hr |
| Device and PC 1224 | 3.8 BTU/hr |
| Device, PC 1224, and power supply | 4.6 BTU/hr |
| Mounting | Mounting base provided
Recommended mounting height: 8 feet with a max mounting height of 12 feet |
| Enclosure type | Plastic |
| Enclosure dimensions | |
| OCS 100C | 4.50" W x 1.40" D
(114 mm W x 36 mm D) |
| |  |
| OCS 100W | 2.80" W x 5.50" L x 2.10" D
(71 mm W x 140 mm x 53 mm D) |
| |  |
| PC 1224 | 1.16" W x 1.16" L x 0.63" D
(30 mm W x 30 mm L x 16 mm D) |
| Product weight | 0.1 lb (<0.1 kg) |
| Color | Off-white |
| Regulatory compliance | CE, c-UL, UL, FCC Class A, KC Complies with appropriate requirements of RoHS, WEEE, and California Title 24 |
| Product warranty | 3 years parts and labor |
| Everlast power supply warranty | 7 years parts and labor |
| NOTE | Specifications are subject to change without notice. |
|